WM-Y90 unit technical data
| Output Power (kVA) |
112.5/125 |
|||||||
|
Output Power (kW) |
90/100 |
|||||||
|
Power Factor |
0.8 (Lagging) |
|||||||
|
Frequency (HZ) |
50 |
|||||||
|
Output Voltage (V) |
400 / 230 |
|||||||
|
Maximum (Long-term/Standby) Output Current (A) |
162/180 |
|||||||
|
Unit Dimensions (Length × Width × Height) (mm) |
2100×860×1400 |
|||||||
|
Unit Net Weight (kg) |
1350 |
|||||||
|
Diesel Engine |
|
|||||||
|
Manufacturer |
Yuchai Group |
|||||||
|
Model |
YC4D155-D30 |
Rated Speed (RPM) |
1500 |
|||||
|
Number of Cylinders |
4 |
Output Power (kW) |
113 |
|||||
|
Cylinder Arrangement |
L |
Fuel Specifications and Grade |
China 0# (Light Diesel) |
|||||
|
Bore/Stroke (mm) |
108/115 |
Noise dB(A) |
96 |
|||||
|
Total Cylinder Capacity (L) |
4.21 |
Minimum Fuel Consumption Rate |
≤205 |
|||||
|
Compression Ratio |
16.7:1 |
Lubricating Oil Specifications and Grade |
API-CG4 and above |
|||||
|
Intake Method |
Turbocharged Intercooled |
Total Lubricating Oil Capacity (L) |
13 |
|||||
|
Speed Control Method |
Electronic Controlled High-Pressure Common Rail |
Lubricating Oil Consumption (g/kwh) |
1.09 |
|||||
|
Starting Method |
Electric Start |
Normal Operating Temperature of Lubricating Oil (℃) |
121 |
|||||
|
Allowable Maximum Back Pressure (kPa) |
10 |
Maximum Exhaust Temperature (℃) |
543 |
|||||
|
Cooling Method |
Closed-circuit Water Cooling |
Air Consumption (m3/min) |
4.4 |
|||||
|
Total Cooling Water Capacity (L) |
19 |
Intake Airflow (m3/min) |
6.15 |
|||||
|
Normal Operating Temperature of Cooling Water (℃) |
82-93 |
Total Dry Weight of Diesel Engine (kg) |
525 |
|||||
|
Cooling Water Flow Rate (L/sec) |
2.36 |
Overall Dimensions Including Water Tank (mm) |
1403×740×1003 |
|||||
|
Generator |
|
|||||||
|
Manufacturer |
Jiangsu Weiming Power Generation Equipment Co., Ltd. |
|
||||||
|
Model |
WM96 |
Excitation Method |
Brushless Self-excited (Optional Auxiliary Winding) |
|||||
|
Voltage Regulation Range |
≥±5% |
Steady-state Voltage Regulation Rate |
≤±1.0% |
|||||
|
Temperature Rise |
H |
Voltage Control Method |
AVR |
|||||
|
Insulation Class |
H |
Overload Capacity |
1.5 times for 2 minutes |
|||||
|
Protection Class |
IP22 |
Short Circuit Capacity |
3 times for 10 seconds |
|||||
|
Efficiency |
93.6% |
Cooling Method |
Self-cooled |
|||||
|
Telephone Interference Coefficient |
THF<2%, TIF<50 |
Rotor Type |
Salient-pole |
|||||
Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.
Keywords:
Previous Page
Next Page
Previous Page:
Next Page:
Recommended News
What are the uses of diesel generator sets?
2020-12-26
The working principle of the generator set
2020-03-12
2020-03-12
Some precautions for using a generator
2020-03-12