WM-C300 unit technical data


WM-C300 Unit Technical Data

Output Capacity (kVA) 337.5/ 375
Output Power (kW) 270/ 300
Power Factor 0.8 (Lagging)
Frequency (Hz) 50
Output Voltage (V) 400 / 230
Maximum (Long-term/Standby) Output Current (A) 486/ 540
Unit Dimensions (Length × Width × Height) (mm) 3100×1030×1780
Unit Net Weight (kg) 3000
Diesel Engine
Manufacturer Chongqing Cummins (CCEC)
Model NTA855-G2A Rated Speed (RPM) 1500
Number of Cylinders 6 Output Power (kW) 343
Cylinder Arrangement L Fuel Specifications and Grade China 0# (Light Diesel)
Bore/Stroke (mm) 140/152 Fuel Consumption (L/h) 70
Total Cylinder Capacity (L) 14 Fuel Consumption (g/kwh) ≤202
Compression Ratio 14:1 Lubricating Oil Specifications and Grade API-CD Grade and Above
Intake Method Turbocharged Total Lubricating Oil Capacity (L) 38.6
Speed Control Method Electronic Governor Lubricating Oil Consumption (L/h) 0.26
Thermostat Adjustment Temperature Range (℃) DC12V Electric Start Normal Operating Temperature of Lubricating Oil (℃) 110
Allowable Maximum Back Pressure (KPa) 10 Maximum Exhaust Temperature (℃) 550
Cooling Method Closed-circuit Water Cooling Intake Airflow (m3/min) 23.7/25.5
Coolant Capacity (L) 65 Exhaust Gas Flow (m3/min) 62.8/67.5
Normal Operating Temperature of Cooling Water (℃) 83-95 Air Consumption (m3/min) 39.1
Cooling Water Flow (L/sec) 5.4 Radiator Dimensions (Length × Width × Height) (mm) 310×995×1350
Generator
Manufacturer Jiangsu Weiming Power Generation Equipment Co., Ltd.
Model WM 38BC Excitation Method Brushless Self-excited (PMG Optional)
Voltage Adjustment Range ≥±5% Steady-state Voltage Regulation Rate ≤±1.0%
Temperature Rise H Voltage Control Method AVR
Insulation Class H Overload Capacity 1.5 times for 2 minutes
Protection Class IP22 Short-circuit Capacity 3 times for 10 seconds
Efficiency 92.65% Cooling Method Self-cooled
Telephone Interference Coefficient THF<2%, TIF<50 Rotor Type Salient-pole

Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.