WM-W75 unit technical data
Output capacity (kVA) | 93.75 / 102.5 | |||||||
Output power (kW) | 75 / 82 | |||||||
Power factor | 0.8 (lagging) | |||||||
Frequency (Hz) | 50 | |||||||
Output voltage (V) | 400/230 | |||||||
Maximum (long-term/standby) output current (A) | 135 / 147.6 | |||||||
Unit dimensions (length × width × height) (mm) | 2200*800*1340 | |||||||
Unit net weight (kg) | 1100 | |||||||
Diesel engine | ||||||||
Manufacturer | Weichai Power Co., Ltd. | |||||||
Model | WP4D100E200 | Rated speed (RPM) | 1500 | |||||
Number of cylinders | 4 | Output power (kW) | 90/100 | |||||
Cylinder arrangement | L | Fuel specifications and grade | China 0# (light diesel) | |||||
Bore/stroke (mm) | 105*130 | Fuel consumption (L/h) | 66 | |||||
Total cylinder capacity (L) | 14 | Fuel consumption (g/kwh) | ≤198 | |||||
Compression ratio | 18:1 | Lubricating oil specifications and grade | API-CD grade and above | |||||
Intake method | Turbocharged | Total lubricating oil capacity (L) | 10 | |||||
Speed control method | Mechanical/electronic control | Lubricating oil consumption (L/h) | 0.26 | |||||
Starting method | Electric start DC12V | Normal operating temperature of lubricating oil (℃) | 110 | |||||
Maximum allowable back pressure (kPa) | 10 | Maximum exhaust temperature (℃) | 550 | |||||
Cooling method | Closed-circuit water cooling | Intake air flow (m3/min) | 22.5/25.1 | |||||
Total cooling water capacity (L) | 5.3 | Exhaust gas flow (m3/min) | 58.8/65.4 | |||||
Normal operating temperature of cooling water (℃) | 83-95 | Air consumption (m3/min) | 36.3 | |||||
Cooling water flow (L/sec) | 5.4 | Radiator dimensions (length × width × height) (mm) | 310×995×1350 | |||||
Generator | ||||||||
Manufacturer | Jiangsu Weiming Power Generation Equipment Co., Ltd. | |||||||
Model | WM 31BJ | Excitation method | Brushless self-excited (PMG optional) | |||||
Voltage adjustment range | ≥±5% | Steady-state voltage regulation rate | ≤±1.0% | |||||
Temperature rise | H | Voltage control method | AVR | |||||
Insulation class | H | Overload capacity | 1.5 times for 2 minutes | |||||
Protection class | IP22 | Short-circuit capacity | 3 times for 10 seconds | |||||
Efficiency | 92.77% | Cooling method | Self-cooled | |||||
Telephone interference coefficient | THF<2%, TIF<50 | Rotor type | Salient-pole type |
Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.
Keywords:
Previous Page
Next Page
Previous Page:
Next Page:
Recommended News
What are the uses of diesel generator sets?
2020-12-26
The working principle of the generator set
2020-03-12
2020-03-12
Some precautions for using a generator
2020-03-12