WM-KP460 unit technical data


Output capacity (kVA)

575

Output power (kW)

460

Power factor

0.8 (lagging)

Frequency (HZ)

50

Output voltage (V)

400 / 230

Maximum (long-term/standby) output current (A)

828

Unit dimensions (length × width × height) (mm)

4000*1300*1900

Net weight of unit (kg)

3900

Diesel engine

 

Manufacturer

Shanghai Kaisun Engine Co., Ltd.

Model

KPV510

Rated speed (RPM)

1500

Number of cylinders

12

Output power (kW)

510

Cylinder arrangement

L

Fuel specifications and grade

China 0# (light diesel)

Bore/stroke (mm)

135*150

Fuel consumption (L/h)

106

Total cylinder capacity (L)

18.9

Fuel consumption (g/kwh)

≤198

Compression ratio

17:1

Lubricating oil specifications and grade

API-CD grade and above

Intake method

Turbocharged

Total lubricating oil capacity (L)

24

Speed control method

Electronic control

Lubricating oil consumption (L/h)

0.43

Thermostat adjustment temperature range (°C)

Electric start DC12V

Normal operating temperature of lubricating oil (°C)

110

Maximum allowable back pressure (KPa)

10

Maximum exhaust temperature (°C)

550

Cooling method

Closed-circuit water cooling

Intake air flow (m3/min)

29.2/32

Coolant capacity (L)

25

Exhaust gas flow (m3/min)

80.7/89.3

Normal operating temperature of cooling water (°C)

83-95

Air consumption (m3/min)

51.5

Cooling water flow (L/sec)

5.4

Radiator dimensions (length × width × height) (mm)

340×1240×1510

Generator

 

Manufacturer

Jiangsu Weiming Power Equipment Co., Ltd.

Model

WM 38BG

Excitation method

Brushless self-excited (PMG optional)

Voltage adjustment range

≥±5%

Steady-state voltage regulation rate

≤±1.0%

Temperature rise

H

Voltage control method

AVR

Insulation class

H

Overload capacity

1.5 times for 2 minutes

Protection class

IP22

Short-circuit capacity

3 times for 10 seconds

Efficiency

93.31%

Cooling method

Self-cooled

Telephone interference coefficient

THF<2%, TIF<50

Rotor type

Salient-pole type

Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.

Keywords: