WM-KP420 unit technical data


WM-KP420 Unit Technical Data


Output Capacity (kVA)

525

Output Power (kW)

420

Power Factor

0.8 (Lagging)

Frequency (HZ)

50

Output Voltage (V)

400 / 230

Maximum (Long-term/Standby) Output Current (A)

756

Unit Dimensions (Length × Width × Height) (mm)

3100*960*1600

Unit Net Weight (kg)

2800

Diesel Engine

 

Manufacturer

Shanghai Kaisun Engine Co., Ltd.

Model

KP475

Rated Speed (RPM)

1500

Number of Cylinders

6

Output Power (kW)

475

Cylinder Arrangement

L

Fuel Specifications and Grade

China 0# (Light Diesel)

Bore/Stroke (mm)

135*168

Fuel Consumption (L/h)

83

Total Cylinder Capacity (L)

14

Fuel Consumption (g/kwh)

≤198

Compression Ratio

17:1

Lubricating Oil Specifications and Grade

API-CD Grade and Above

Intake Method

Turbocharged

Total Lubricating Oil Capacity (L)

24

Speed Control Method

Electronic Control

Lubricating Oil Consumption (L/h)

0.35

Thermostat Adjustment Temperature Range (℃)

Electric Start DC12V

Normal Operating Temperature of Lubricating Oil (℃)

110

Allowable Maximum Back Pressure (KPa)

10

Maximum Exhaust Temperature (℃)

550

Cooling Method

Closed-circuit Water Cooling

Intake Airflow (m3/min)

23.7/25.5

Coolant Capacity (L)

22

Exhaust Airflow (m3/min)

62.8/67.5

Normal Operating Temperature of Cooling Water (℃)

83-95

Air Consumption (m3/min)

39.1

Cooling Water Flow Rate (L/sec)

5.4

Radiator Dimensions (Length × Width × Height) (mm)

310×995×1350

Generator

 

Manufacturer

Jiangsu Weiming Power Generation Equipment Co., Ltd.

Model

WM 38BE

Excitation Method

Brushless Self-excited (PMG Optional)

Voltage Adjustment Range

≥±5%

Steady-state Voltage Regulation Rate

≤±1.0%

Temperature Rise

H

Voltage Control Method

AVR

Insulation Class

H

Overload Capacity

1.5 times for 2 minutes

Protection Class

IP22

Short-circuit Capacity

3 times for 10 seconds

Efficiency

93.37%

Cooling Method

Self-cooled

Telephone Interference Coefficient

THF<2%, TIF<50

Rotor Type

Salient-pole

Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.

 