WM-KP440 unit technical data


WM-KP440 Unit Technical Data

Output Capacity (kVA)

550

Output Power (kW)

440

Power Factor

0.8 (Lagging)

Frequency (HZ)

50

Output Voltage (V)

400 / 230

Maximum (Long-term/Standby) Output Current (A)

792

Unit Dimensions (Length × Width × Height) (mm)

3700*1200*1750

Unit Net Weight (kg)

3600

Diesel Engine

 

Manufacturer

Shanghai Kaisun Engine Co., Ltd.

Model

KPV450

Rated Speed (RPM)

1500

Number of Cylinders

12

Output Power (kW)

450

Cylinder Arrangement

L

Fuel Specifications and Grade

China 0# (Light Diesel)

Bore/Stroke (mm)

135*150

Fuel Consumption (L/h)

97

Total Cylinder Capacity (L)

18.9

Fuel Consumption (g/kwh)

≤198

Compression Ratio

17:1

Lubricating Oil Specifications and Grade

API-CD Grade and Above

Intake Method

Turbocharged

Total Lubricating Oil Capacity (L)

24

Speed Control Method

Electronic Control

Lubricating Oil Consumption (L/h)

0.40

Thermostat Adjustment Temperature Range (°C)

Electric Start DC12V

Normal Operating Temperature of Lubricating Oil (°C)

110

Allowable Maximum Back Pressure (KPa)

10

Maximum Exhaust Temperature (°C)

550

Cooling Method

Closed-circuit Water Cooling

Intake Airflow (m3/min)

29.2/32

Coolant Capacity (L)

22

Exhaust Gas Flow (m3/min)

80.7/89.3

Normal Operating Temperature of Cooling Water (°C)

83-95

Air Consumption (m3/min)

51.5

Cooling Water Flow (L/sec)

5.4

Radiator Dimensions (Length × Width × Height) (mm)

340×1240×1510

Generator

 

Manufacturer

Jiangsu Weiming Power Generation Equipment Co., Ltd.

Model

WM 38BF

Excitation Method

Brushless Self-excited (PMG Optional)

Voltage Adjustment Range

≥±5%

Steady-state Voltage Regulation Rate

≤±1.0%

Temperature Rise

H

Voltage Control Method

AVR

Insulation Class

H

Overload Capacity

1.5 times for 2 minutes

Protection Class

IP22

Short-circuit Capacity

3 times for 10 seconds

Efficiency

93.61%

Cooling Method

Self-cooled

Telephone Interference Coefficient

THF<2%, TIF<50

Rotor Type

Salient-pole

Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.

 