WM-Y160 unit technical data
|
Output Power (kVA) |
200/225 |
|||||||
|
Output Power (kW) |
160/180 |
|||||||
|
Power Factor |
0.8 (Lagging) |
|||||||
|
Frequency (HZ) |
50 |
|||||||
|
Output Voltage (V) |
400 / 230 |
|||||||
|
Maximum (Continuous/Standby) Output Current (A) |
288/324 |
|||||||
|
Unit Dimensions (Length × Width × Height) (mm) |
2800×1000×1450 |
|||||||
|
Unit Net/Gross Weight (kg) |
1900 |
|||||||
|
Diesel Engine |
|
|||||||
|
Manufacturer |
Yuchai Group |
|||||||
|
Model |
YC6A275-D30 |
Rated Speed (RPM) |
1500 |
|||||
|
Number of Cylinders |
6 |
Output Power (kW) |
203 |
|||||
|
Cylinder Arrangement |
L |
Fuel Specifications and Grade |
China 0# (Light Diesel) |
|||||
|
Bore/Stroke (mm) |
108/132 |
Noise dB(A) |
98 |
|||||
|
Total Cylinder Displacement (L) |
7.25 |
Minimum Fuel Consumption Rate (g/kwh) |
≤200 |
|||||
|
Compression Ratio |
17.5:1 |
Lubricating Oil Specifications and Grade |
API-CG4 and above |
|||||
|
Intake Method |
Turbocharged Intercooled |
Total Lubricating Oil Capacity (L) |
22 |
|||||
|
Speed Control Method |
Electronic Controlled High-Pressure Common Rail |
Lubricating Oil Consumption (g/kwh) |
0.6 |
|||||
|
Starting Method |
Electric Start |
Normal Operating Temperature of Lubricating Oil (°C) |
121 |
|||||
|
Allowable Maximum Back Pressure (kPa) |
10 |
Maximum Exhaust Temperature (°C) |
524 |
|||||
|
Cooling Method |
Closed-Cycle Water Cooling |
Air Consumption (m3/min) |
4.4 |
|||||
|
Total Cooling Water Capacity (L) |
27 |
Intake Airflow (m3/min) |
6.15 |
|||||
|
Normal Operating Temperature of Cooling Water (°C) |
88-96 |
Total Dry Weight of Diesel Engine (kg) |
825 |
|||||
|
Cooling Water Flow Rate (L/sec) |
3.9 |
Overall Dimensions Including Water Tank (mm) |
1740×960×1160 |
|||||
|
Generator |
|
|||||||
|
Manufacturer |
Jiangsu Weiming Power Equipment Co., Ltd. |
|
||||||
|
Model |
WM160 |
Excitation Method |
Brushless Self-Excited (Optional PMG) |
|||||
|
Voltage Adjustment Range |
≥±5% |
Steady-State Voltage Regulation Rate |
≤±1.0% |
|||||
|
Temperature Rise |
H |
Voltage Control Method |
AVR |
|||||
|
Insulation Class |
H |
Overload Capacity |
1.5 times for 2 minutes |
|||||
|
Protection Class |
IP22 |
Short Circuit Capacity |
3 times for 10 seconds |
|||||
|
Efficiency |
92.0% |
Cooling Method |
Self-Cooling |
|||||
|
Telephone Interference Coefficient |
THF<2%, TIF<50 |
Rotor Type |
Salient-Pole Type |
|||||
Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.
Keywords:
Previous Page
Next Page
Previous Page:
Next Page:
Recommended News
What are the uses of diesel generator sets?
2020-12-26
The working principle of the generator set
2020-03-12
2020-03-12
Some precautions for using a generator
2020-03-12