Technical data for YCM44D30 unit
YCM44D30 Unit Technical Data
| Output Power (kVA) |
: 50/55 |
|||||||
| Output Power (kW) |
: 40/44 |
|||||||
| Power Factor |
: 0.8 (Lagging) |
|||||||
| Output Voltage (V) |
: 400/230 |
|||||||
| Maximum (Continuous/Standby) Output Current (A) |
: 72 / 79 |
|||||||
| Unit Dimensions (Length × Width × Height) (mm) |
: 1900 × 760 × 1300 |
|||||||
| Unit Net Weight (kg) |
: 970 |
|||||||
| Diesel Engine |
|
|||||||
| Manufacturer |
: Yuchai Group |
|||||||
| Model |
: YC4D75-D34 |
Rated Speed (RPM) |
: 1500 |
|||||
| Number of Cylinders |
: 4 |
Output Power (kW) |
: 59 |
|||||
| Cylinder Arrangement |
: L |
Fuel Specifications and Grade |
: China 0# (Light Diesel) |
|||||
| Bore/Stroke (mm) |
: 108/115 |
Noise dB(A) |
: 102 |
|||||
| Total Cylinder Capacity (L) |
: 4.21 |
Minimum Fuel Consumption Rate (g/kwh) |
: ≤205 |
|||||
| Compression Ratio |
: 17.5:1 |
Lubricating Oil Specifications and Grade |
: API-CD Grade and Above |
|||||
| Intake Method |
: Turbocharged |
Total Lubricating Oil Capacity (L) |
: 13 |
|||||
| Speed Control Method |
: Electronic Controlled High-Pressure Common Rail |
Lubricating Oil Consumption (L/h) |
: 0.04 |
|||||
| Starting Method |
: Electric Start |
Normal Operating Temperature of Lubricating Oil (℃) |
: 110 |
|||||
| Allowable Maximum Back Pressure (kPa) |
: 10 |
Maximum Exhaust Temperature (℃) |
: 480 |
|||||
| Cooling Method |
: Closed-Cycle Water Cooling |
Air Consumption (m3/min) |
: 4.4 |
|||||
| Total Cooling Water Capacity (L) |
: 19 |
Intake Airflow (m3/min) |
: 6.15 |
|||||
| Normal Operating Temperature of Cooling Water (℃) |
: 83-95 |
Total Dry Weight of Diesel Engine (kg) |
: 370 |
|||||
| Cooling Water Flow Rate (L/sec) |
: 1.4 |
Overall Dimensions Including Water Tank (mm) |
: 1100 × 750 × 960 |
|||||
| Generator |
|
|||||||
| Manufacturer |
: Jiangsu Weiming Power Generation Equipment Co., Ltd. |
|
||||||
| Model |
: WM40 |
Excitation Method |
: Brushless Self-Excited (Optional Auxiliary Winding) |
|||||
| Voltage Adjustment Range |
: ≥±6% |
Steady-State Voltage Regulation Rate |
: ≤±1.0% |
|||||
| Temperature Rise |
: H |
Voltage Control Method |
: AVR |
|||||
| Insulation Class |
: H |
Overload Capacity |
: 1.5 times for 2 minutes |
|||||
| Protection Class |
: IP22 |
Short Circuit Capacity |
: 3 times for 10 seconds |
|||||
| Efficiency |
: 87.6% |
Cooling Method |
: Self-Cooling |
|||||
| Telephone Interference Factor |
: THF<2%, TIF<50 |
Rotor Type |
: Salient-pole type |
|||||
Note: The above technical data is for reference only. Our company will not provide further notice if the technical parameters change for various reasons.
Keywords:
Previous Page
Next Page
Previous Page:
Next Page:
Recommended News
What are the uses of diesel generator sets?
2020-12-26
The working principle of the generator set
2020-03-12
2020-03-12
Some precautions for using a generator
2020-03-12