WM-C450 unit technical data
WM-C450 Unit Technical Data
Output Capacity (kVA) | 500/550 | |||||||
Output Power (kW) | 400/440 | |||||||
Power Factor | 0.8 (Lagging) | |||||||
Frequency (HZ) | 50 | |||||||
Output Voltage (V) | 400 / 230 | |||||||
Maximum (Continuous/Standby) Output Current (A) | 720/792 | |||||||
Unit Dimensions (Length × Width × Height) (mm) | 3400×1250×1970 | |||||||
Unit Net Weight (kg) | 3650 | |||||||
Diesel Engine | ||||||||
Manufacturer | Chongqing Cummins (CCEC) | |||||||
Model | KTA19-G4 | Rated Speed (RPM) | 1500 | |||||
Number of Cylinders | 6 | Output Power (kW) | 504 | |||||
Cylinder Arrangement | L | Fuel Specifications and Grade | China 0# (Light Diesel) | |||||
Bore/Stroke (mm) | 159/159 | Fuel Consumption (L/h) | 107 | |||||
Total Cylinder Capacity (L) | 18.9 | Fuel Consumption (g/kwh) | ≤202 | |||||
Compression Ratio | 14.5:1 | Lubricating Oil Specifications and Grade | API-CD Grade and Above | |||||
Intake Method | Turbocharged | Total Lubricating Oil Capacity (L) | 50 | |||||
Speed Control Method | Electronic Governor | Lubricating Oil Consumption (L/h) | 0.48 | |||||
Thermostat Adjustment Temperature Range (°C) | DC12V Electric Start | Normal Operating Temperature of Lubricating Oil (°C) | 110 | |||||
Allowable Maximum Back Pressure (KPa) | 10 | Maximum Exhaust Temperature (°C) | 550 | |||||
Cooling Method | Closed-Circuit Water Cooling | Intake Airflow (m3/min) | 31.9/34.7 | |||||
Coolant Capacity (L) | 98 | Exhaust Gas Flow (m3/min) | 86/96.2 | |||||
Normal Operating Temperature of Cooling Water (°C) | 83-95 | Air Consumption (m3/min) | 54.1 | |||||
Cooling Water Flow (L/sec) | 5.4 | Radiator Dimensions (Length × Width × Height) (mm) | 340×1240×1510 | |||||
Generator | ||||||||
Manufacturer | Jiangsu Weiming Power Generation Equipment Co., Ltd. | |||||||
Model | WM 38BG | Excitation Method | Brushless Self-Excited (PMG Optional) | |||||
Voltage Regulation Range | ≥±5% | Steady-State Voltage Regulation Rate | ≤±1.0% | |||||
Temperature Rise | H | Voltage Control Method | AVR | |||||
Insulation Class | H | Overload Capacity | 1.5 times for 2 minutes | |||||
Protection Class | IP22 | Short Circuit Capacity | 3 times for 10 seconds | |||||
Efficiency | 93.31% | Cooling Method | Self-Cooling | |||||
Telephone Interference Coefficient | THF<2%, TIF<50 | Rotor Type | Salient-Pole Type |
Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.
Keywords:
Previous Page
Next Page
Previous Page:
Next Page:
Recommended News
What are the uses of diesel generator sets?
2020-12-26
The working principle of the generator set
2020-03-12
2020-03-12
Some precautions for using a generator
2020-03-12