WM-KP1000 unit technical data
| Output capacity (kVA) |
1250 |
|||||||
|
Output power (kW) |
1000 |
|||||||
|
Power factor |
0.8 (lagging) |
|||||||
|
Frequency (Hz) |
50 |
|||||||
|
Output voltage (V) |
400 / 230 |
|||||||
|
Maximum (long-term/standby) output current (A) |
1800 |
|||||||
|
Unit dimensions (length × width × height) (mm) |
4700*1650*2200 |
|||||||
|
Net weight of unit (kg) |
6200 |
|||||||
|
Diesel engine |
|
|||||||
|
Manufacturer |
Shanghai Kaisun Engine Co., Ltd. |
|||||||
|
Model |
KPV1200 |
Rated speed (RPM) |
1500 |
|||||
|
Number of cylinders |
12 |
Output power (kW) |
1160 |
|||||
|
Cylinder arrangement |
V |
Fuel specifications and grade |
China 0# (light diesel) |
|||||
|
Bore/stroke (mm) |
138*165 |
Fuel consumption (L/h) |
274 |
|||||
|
Total cylinder capacity (L) |
50.3 |
Fuel consumption (g/kwh) |
≤198 |
|||||
|
Compression ratio |
15:1 |
Lubricating oil specifications and grade |
API-CD grade and above |
|||||
|
Intake method |
Turbocharged |
Total lubricating oil capacity (L) |
146 |
|||||
|
Speed control method |
Electronic control |
Lubricating oil consumption (L/h) |
1.37 |
|||||
|
Thermostat adjustment temperature range (℃) |
Electric start DC12V |
Normal operating temperature of lubricating oil (℃) |
110 |
|||||
|
Allowable maximum back pressure (KPa) |
10 |
Maximum exhaust temperature (℃) |
550 |
|||||
|
Cooling method |
Closed-circuit water cooling |
Intake air flow (m3/min) |
96.2 |
|||||
|
Coolant capacity (L) |
83 |
Exhaust gas flow (m3/min) |
223.6 |
|||||
|
Normal operating temperature of cooling water (℃) |
83-95 |
Air consumption (m3/min) |
131.4 |
|||||
|
Cooling water flow (L/sec) |
5.4 |
Radiator dimensions (length × width × height) (mm) |
410×1745×2025 |
|||||
|
Generator |
|
|||||||
|
Manufacturer |
Jiangsu Weiming Power Generation Equipment Co., Ltd. |
|||||||
|
Model |
WM 48OD |
Excitation method |
Brushless self-excited (PMG optional) |
|||||
|
Voltage adjustment range |
≥±5% |
Steady-state voltage regulation rate |
≤±1.0% |
|||||
|
Temperature rise |
H |
Voltage control method |
AVR |
|||||
|
Insulation class |
H |
Overload capacity |
1.5 times for 2 minutes |
|||||
|
Protection class |
IP22 |
Short-circuit capacity |
3 times for 10 seconds |
|||||
|
Efficiency |
95.8% |
Cooling method |
Self-cooled |
|||||
|
Telephone interference coefficient |
THF<2%, TIF<50 |
Rotor type |
Salient-pole type |
|||||
Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.