WM-KP600 unit technical data


WM-KP600 Unit Technical Data

Output Capacity (kVA)

750

Output Power (kW)

600

Power Factor

0.8 (Lagging)

Frequency (Hz)

50

Output Voltage (V)

400 / 230

Maximum (Long Run/Standby) Output Current (A)

1080

Unit Dimensions (Length × Width × Height) (mm)

4500*1520*2100

Unit Net Weight (kg)

4000

Diesel Engine

 

Manufacturer

Shanghai Kaisun Engine Co., Ltd.

Model

KPV630

Rated Speed (RPM)

1500

Number of Cylinders

12

Output Power (kW)

630

Cylinder Arrangement

L

Fuel Specifications and Grade

China 0# (Light Diesel)

Bore/Stroke (mm)

135*150

Fuel Consumption (L/h)

139

Total Cylinder Capacity (L)

18.9

Fuel Consumption (g/kwh)

≤198

Compression Ratio

17:1

Lubricating Oil Specifications and Grade

API-CD Grade and Above

Intake Method

Turbocharged

Total Lubricating Oil Capacity (L)

36

Speed Control Method

Electronic Control

Lubricating Oil Consumption (L/h)

0.7

Thermostat Adjustment Temperature Range (℃)

Electric Start DC12V

Normal Operating Temperature of Lubricating Oil (℃)

110

Allowable Maximum Back Pressure (KPa)

10

Maximum Exhaust Temperature (℃)

550

Cooling Method

Closed-Circuit Water Cooling

Intake Airflow (m3/min)

41.5/43.9

Coolant Capacity (L)

25

Exhaust Gas Flow (m3/min)

111.3/119.5

Normal Operating Temperature of Cooling Water (℃)

83-95

Air Consumption (m3/min)

69.8

Cooling Water Flow (L/sec)

5.4

Radiator Dimensions (Length × Width × Height) (mm)

340×1240×1510

Generator

 

Manufacturer

Jiangsu Weiming Power Generation Equipment Co., Ltd.

Model

WM 38BH

Excitation Method

Brushless Self-Excited (PMG Optional)

Voltage Adjustment Range

≥±5%

Steady-State Voltage Regulation Rate

≤±1.0%

Temperature Rise

H

Voltage Control Method

AVR

Insulation Class

H

Overload Capacity

1.5 times for 2 minutes

Protection Class

IP22

Short Circuit Capacity

3 times for 10 seconds

Efficiency

93.89%

Cooling Method

Self-Cooling

Telephone Interference Coefficient

THF<2%, TIF<50

Rotor Type

Salient-Pole Type

Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.