WM-W45 unit technical data
Output capacity (kVA) | 55/62.5 | |||||||
Output power (kW) | 44/50 | |||||||
Power factor | 0.8 (lagging) | |||||||
Frequency (Hz) | 50 | |||||||
Output voltage (V) | 400 / 230 | |||||||
Maximum (standby) output current (A) | 79.2/90 | |||||||
Unit dimensions (length × width × height) (mm) | 1700*650*1180 | |||||||
Unit net weight (kg) | 820 | |||||||
Diesel engine | ||||||||
Manufacturer | Weichai Power Co., Ltd. | |||||||
Model | WP2.3ND60E310 | Rated speed (RPM) | 1500 | |||||
Number of cylinders | 4 | Output power (kW) | 55/60.5 | |||||
Cylinder arrangement | V | Fuel specifications and grade | China 0# (light diesel) | |||||
Bore/stroke (mm) | 89*92 | Fuel consumption (L/h) | 265 | |||||
Total cylinder capacity (L) | 37.8 | Fuel consumption (g/kwh) | ≤210 | |||||
Compression ratio | 17.5:1 | Lubricating oil specifications and grade | API-CD grade and above | |||||
Intake method | Turbocharged | Total lubricating oil capacity (L) | 8 | |||||
Speed control method | Electronic controlled high-pressure common rail | Lubricating oil consumption (L/h) | 1.5 | |||||
Thermostat adjustment temperature range (°C) | Electric start DC12V | Normal operating temperature of lubricating oil (°C) | 110 | |||||
Allowable maximum back pressure (KPa) | 10 | Maximum exhaust temperature (°C) | 550 | |||||
Cooling method | Closed-loop water cooling | Intake air flow (m3/min) | 62.5/67.6 | |||||
Coolant capacity (L) | 5 | Exhaust gas flow (m3/min) | 176.2/193.5 | |||||
Normal operating temperature of cooling water (°C) | 83-95 | Air consumption (m3/min) | 113.7 | |||||
Cooling water flow (L/sec) | 5.4 | Radiator dimensions (length × width × height) (mm) | 410×1745×2025 | |||||
Generator | ||||||||
Manufacturer | Jiangsu Weiming Power Generation Equipment Co., Ltd. | |||||||
Model | WM 48OD | Excitation method | Brushless self-excited (PMG optional) | |||||
Voltage adjustment range | ≥±5% | Steady-state voltage regulation rate | ≤±1.0% | |||||
Temperature rise | H | Voltage control method | AVR | |||||
Insulation class | H | Overload capacity | 1.5 times for 2 minutes | |||||
Protection class | IP22 | Short-circuit capacity | 3 times for 10 seconds | |||||
Efficiency | 95.8% | Cooling method | Self-cooled | |||||
Telephone interference coefficient | THF<2%, TIF<50 | Rotor type | Salient-pole type |
Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.
Keywords:
Previous Page
Next Page
Previous Page:
Next Page:
Recommended News
What are the uses of diesel generator sets?
2020-12-26
The working principle of the generator set
2020-03-12
2020-03-12
Some precautions for using a generator
2020-03-12