WM-W20 unit technical data

Output capacity (kVA) |
25/31.25 |
|||||||
Output power (kW) |
20/25 |
|||||||
Power factor |
0.8 (lagging) |
|||||||
Frequency (Hz) |
50 |
|||||||
Output voltage (V) |
400 / 230 |
|||||||
Maximum (long-term/standby) output current (A) |
36/45 |
|||||||
Unit dimensions (length × width × height) (mm) |
1550*630*1150 |
|||||||
Unit net weight (kg) |
650 |
|||||||
Diesel engine |
|
|||||||
Manufacturer |
Weichai Power Co., Ltd. |
|||||||
Model |
WP2.3ND28E310 |
Rated speed (RPM) |
1500 |
|||||
Number of cylinders |
4 |
Output power (kW) |
25/27.5 |
|||||
Cylinder arrangement |
V |
Fuel specifications and grade |
China 0# (light diesel) |
|||||
Bore/stroke (mm) |
89*92 |
Fuel consumption (L/h) |
299 |
|||||
Total cylinder capacity (L) |
50.3 |
Fuel consumption (g/kwh) |
≤210 |
|||||
Compression ratio |
17.5:1 |
Lubricating oil specifications and grade |
API-CD grade and above |
|||||
Intake method |
Turbocharged |
Total lubricating oil capacity (L) |
8 |
|||||
Speed control method |
Electronic controlled high-pressure common rail |
Lubricating oil consumption (L/h) |
1.725 |
|||||
Thermostat adjustment temperature range (°C) |
Electric start DC12V |
Normal operating temperature of lubricating oil (°C) |
110 |
|||||
Allowable maximum back pressure (KPa) |
10 |
Maximum exhaust temperature (°C) |
550 |
|||||
Cooling method |
Closed-loop water cooling |
Intake air flow (m3/min) |
62.5/67.6 |
|||||
Coolant capacity (L) |
5 |
Exhaust gas flow (m3/min) |
176.2/193.5 |
|||||
Normal operating temperature of cooling water (°C) |
83-95 |
Air consumption (m3/min) |
113.7 |
|||||
Cooling water flow (L/sec) |
5.4 |
Radiator dimensions (length × width × height) (mm) |
410×1745×2025 |
|||||
Generator |
|
|||||||
Manufacturer |
Jiangsu Weiming Power Generation Equipment Co., Ltd. |
|||||||
Model |
WM 48OF |
Excitation method |
Brushless self-excited (PMG optional) |
|||||
Voltage adjustment range |
≥±5% |
Steady-state voltage regulation rate |
≤±1.0% |
|||||
Temperature rise |
H |
Voltage control method |
AVR |
|||||
Insulation class |
H |
Overload capacity |
1.5 times for 2 minutes |
|||||
Protection class |
IP22 |
Short-circuit capacity |
3 times for 10 seconds |
|||||
Efficiency |
95.7% |
Cooling method |
Self-cooled |
|||||
Telephone interference coefficient |
THF<2%, TIF<50 |
Rotor type |
Salient-pole type |
Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.