WM-P520 unit technical data


Output capacity (kVA) 600/650
Output power (kW) 480/520
Power factor 0.8 (lagging)
Frequency (Hz) 50
Output voltage (V) 400 / 230
Maximum (long-term/standby) output current (A) 864/936
Unit dimensions (length × width × height) (mm) 4100*1600*2200
Unit net weight (kg) 4600
Diesel engine  
Manufacturer Perkins Engines Company Limited (UK)
Model 2806C-E18TAG1A Rated speed (RPM) 1500
Number of cylinders 6 Output power (kW) 480/514
Cylinder arrangement V Fuel specifications and grade China 0# (light diesel)
Bore/stroke (mm) 145*183 Fuel consumption (L/h) 209
Total cylinder capacity (L) 37.8 Fuel consumption (g/kwh) ≤216
Compression ratio 15:1 Lubricating oil specifications and grade API-CD grade and above
Intake method Turbocharged Total lubricating oil capacity (L) 62
Speed control method Electronic control Lubricating oil consumption (L/h) 0.86
Thermostat adjustment temperature range (°C) Electric start DC12V Normal operating temperature of lubricating oil (°C) 110
Allowable maximum back pressure (KPa) 10 Maximum exhaust temperature (°C) 550
Cooling method Closed-circuit water cooling Intake air flow (m3/min) 68.4/72.8
Coolant capacity (L) 83 Exhaust gas flow (m3/min) 183/198.4
Normal operating temperature of cooling water (°C) 83-95 Air consumption (m3/min) 114.6
Cooling water flow (L/sec) 5.4 Radiator dimensions (length × width × height) (mm) 410×1745×2040
Generator  
Manufacturer Jiangsu Weiming Power Generation Equipment Co., Ltd.
Model WM 42OE Excitation method Brushless self-excited (PMG optional)
Voltage regulation range ≥±5% Steady-state voltage regulation rate ≤±1.0%
Temperature rise H Voltage control method AVR
Insulation class H Overload capacity 1.5 times for 2 minutes
Protection class IP22 Short-circuit capacity 3 times for 10 seconds
Efficiency 95.2% Cooling method Self-cooled
Telephone interference coefficient THF<2%, TIF<50 Rotor type Salient-pole type

Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.

Keywords: