WM-P176 unit technical data


Output Capacity (kVA) 200/220
Output Power (kW) 160/176
Power Factor 0.8 (Lagging)
Frequency (HZ) 50
Output Voltage (V) 400 / 230
Maximum (Continuous/Standby) Output Current (A) 288/316.8
Unit Dimensions (Length × Width × Height) (mm) 2800*950*1450
Unit Net Weight (kg) 2100
Diesel Engine  
Manufacturer Perkins Engines Company Limited (UK)
Model 1106A-70TAG4 Rated Speed (RPM) 1500
Number of Cylinders 6 Output Power (kW) 160/202
Cylinder Arrangement L Fuel Specifications and Grade China 0# (Light Diesel)
Bore/Stroke (mm) 105*135 Fuel Consumption (L/h) 107
Total Cylinder Capacity (L) 18.9 Fuel Consumption (g/kwh) ≤220
Compression Ratio 16:1 Lubricating Oil Specifications and Grade API-CD Grade and Above
Intake Method Turbocharged Total Lubricating Oil Capacity (L) 16.5
Speed Control Method Mechanical/Electronic Control Lubricating Oil Consumption (L/h) 0.48
Thermostat Adjustment Temperature Range (°C) DC12V Electric Start Normal Operating Temperature of Lubricating Oil (°C) 110
Allowable Maximum Back Pressure (KPa) 10 Maximum Exhaust Temperature (°C) 550
Cooling Method Closed-Circuit Water Cooling Intake Airflow (m3/min) 31.9/34.7
Coolant Capacity (L) 25 Exhaust Gas Flow (m3/min) 86/96.2
Normal Operating Temperature of Cooling Water (°C) 83-95 Air Consumption (m3/min) 54.1
Cooling Water Flow (L/sec) 5.4 Radiator Dimensions (Length × Width × Height) (mm) 340×1240×1510
Generator  
Manufacturer Jiangsu Weiming Power Generation Equipment Co., Ltd.
Model WM 38BG Excitation Method Brushless Self-Excited (PMG Optional)
Voltage Regulation Range ≥±5% Steady-State Voltage Regulation Rate ≤±1.0%
Temperature Rise H Voltage Control Method AVR
Insulation Class H Overload Capacity 1.5 times for 2 minutes
Protection Class IP22 Short Circuit Capacity 3 times for 10 seconds
Efficiency 93.31% Cooling Method Self-Cooling
Telephone Interference Coefficient THF<2%, TIF<50 Rotor Type Salient-Pole Type

Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.

Keywords: