WMP8 unit technical data
WMP8 Genset Technical Data
| Output Capacity (kVA) |
: 8.75/10 |
|||||||
| Output Power (kW) |
: 7/8 |
|||||||
| Power Factor |
: 0.8 (Lagging) |
|||||||
| Frequency (Hz) |
: 50 |
|||||||
| Output Voltage (V) |
: 400/230 |
|||||||
| Maximum (Continuous/Standby) Output Current (A) |
: 12.6/14.4 |
|||||||
| Genset Dimensions (L×W×H) (mm) |
: 1200*700*1100 |
|||||||
| Genset Net Weight (kg) |
: 300 |
|||||||
| Diesel Engine |
|
|||||||
| Manufacturer |
: Perkins Engines Company Limited (UK) |
|||||||
| Model |
: 403D-11G |
Rated Speed (RPM) |
: 1500 |
|||||
| Number of Cylinders |
: 3 |
Output Power (kW) |
: 7.2/9.3 |
|||||
| Cylinder Arrangement |
: L |
Fuel Specifications and Grade |
: China 0# (Light Diesel) |
|||||
| Bore/Stroke (mm) |
: 77*81 |
Fuel Consumption (L/h) |
: 53.4 |
|||||
| Total Cylinder Capacity (L) |
: 14 |
Fuel Consumption (g/kwh) |
: ≤252 |
|||||
| Compression Ratio |
: 16.4:1 |
Lubricating Oil Specifications and Grade |
: API-CD Grade and Above |
|||||
| Intake Method |
: Turbocharged |
Total Lubricating Oil Capacity (L) |
: 4.9 |
|||||
| Speed Control Method |
: Mechanical/Electronic Control |
Lubricating Oil Consumption (L/h) |
: 0.24 |
|||||
| Starting Method |
: DC12V Electric Start |
Normal Operating Temperature of Lubricating Oil (℃) |
: 110 |
|||||
| Allowable Maximum Back Pressure (kPa) |
: 10.0 |
Maximum Exhaust Temperature (℃) |
: 550 |
|||||
| Cooling Method |
: Closed-Cycle Water Cooling |
Intake Airflow (m3/min) |
: 19.44/21.06 |
|||||
| Total Cooling Water Capacity (L) |
: 15 |
Exhaust Gas Flow (m3/min) |
: 53.64/58.02 |
|||||
| Normal Operating Temperature of Cooling Water (℃) |
: 83-95 |
Air Consumption (m3/min) |
: 34.2 |
|||||
| Cooling Water Flow (L/sec) |
: 5.4 |
Radiator Dimensions (L×W×H) (mm) |
: 310×995×1350 |
|||||
| Generator |
|
|||||||
| Manufacturer |
: Jiangsu Weiming Power Generation Equipment Co., Ltd. |
|
||||||
| Model |
: WM 31BG |
Excitation Method |
: Brushless Self-Excited (PMG Optional) |
|||||
| Voltage Regulation Range |
: ≥±5% |
Steady-State Voltage Regulation Rate |
: ≤±1.0% |
|||||
| Temperature Rise |
: H |
Voltage Control Method |
: AVR |
|||||
| Insulation Class |
: H |
Overload Capacity |
: 1.5 times for 2 minutes |
|||||
| Protection Class |
: IP22 |
Short Circuit Capacity |
: 3 times for 10 seconds |
|||||
| Efficiency |
: 91.89% |
Cooling Method |
: Self-cooling type |
|||||
| Telephone interference coefficient |
: THF < 2%, TIF < 50 |
Rotor type |
: Salient-pole type |
|||||
Note: The above technical data is for reference only. Our company will not provide further notice if the technical parameters change due to various reasons.