WM-HD470 unit technical data
| Output Capacity (kVA) | 537.5/587.5 |
|||||||
| Output Power (kW) |
430/470 |
|||||||
| Power Factor |
0.8 (Lagging) |
|||||||
| Frequency (HZ) |
50 |
|||||||
| Output Voltage (V) |
400 / 230 |
|||||||
| Maximum (Continuous/Standby) Output Current (A) |
774/846 |
|||||||
| Unit Dimensions (Length × Width × Height) (mm) |
3300*1440*2160 |
|||||||
| Unit Net Weight (kg) |
3630 |
|||||||
| Diesel Engine |
|
|||||||
| Manufacturer |
Deutz |
|||||||
| Model |
BF8M1015CP-LA G4 |
Rated Speed (RPM) |
1500 |
|||||
| Number of Cylinders |
8 |
Output Power (kW) |
480/530 |
|||||
| Cylinder Arrangement |
L |
Fuel Specifications and Grade |
China 0# (Light Diesel) |
|||||
| Bore/Stroke (mm) |
132*145 |
Fuel Consumption (L/h) |
106 |
|||||
| Total Cylinder Capacity (L) |
18.9 |
Fuel Consumption (g/kwh) |
≤196 |
|||||
| Compression Ratio |
17.5:1 |
Lubricating Oil Specifications and Grade |
API-CD Grade and Above |
|||||
| Intake Method |
Turbocharged |
Total Lubricating Oil Capacity (L) |
48 |
|||||
| Speed Control Method |
Electronic Governor |
Lubricating Oil Consumption (L/h) |
0.43 |
|||||
| Thermostat Adjustment Temperature Range (℃) |
DC12V Electric Start |
Normal Operating Temperature of Lubricating Oil (℃) |
110 |
|||||
| Allowable Maximum Back Pressure (KPa) |
10 |
Maximum Exhaust Temperature (℃) |
550 |
|||||
| Cooling Method |
Closed-Circuit Water Cooling |
Intake Airflow (m3/min) |
29.2/32 |
|||||
| Coolant Capacity (L) |
98 |
Exhaust Airflow (m3/min) |
80.7/89.3 |
|||||
| Normal Operating Temperature of Cooling Water (℃) |
83-95 |
Air Consumption (m3/min) |
51.5 |
|||||
| Cooling Water Flow Rate (L/sec) |
5.4 |
Radiator Dimensions (Length × Width × Height) (mm) |
340×1240×1510 |
|||||
| Generator |
|
|||||||
| Manufacturer |
Jiangsu Weiming Power Generation Equipment Co., Ltd. |
|||||||
| Model |
WM 38BG |
Excitation Method |
Brushless Self-Excited (PMG Optional) |
|||||
| Voltage Adjustment Range |
≥±5% |
Steady-State Voltage Regulation Rate |
≤±1.0% |
|||||
| Temperature Rise |
H |
Voltage Control Method |
AVR |
|||||
| Insulation Class |
H |
Overload Capacity |
1.5 times for 2 minutes |
|||||
| Protection Class |
IP22 |
Short Circuit Capacity |
3 times for 10 seconds |
|||||
| Efficiency |
93.31% |
Cooling Method |
Self-Cooling |
|||||
| Telephone Interference Coefficient |
THF<2%, TIF<50 |
Rotor Type |
Salient-Pole Type |
|||||
Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.