WM-HD440 unit technical data
| Output capacity (kVA) |
500/550 |
|||||||
| Output power (kW) |
400/440 |
|||||||
| Power factor |
0.8 (lagging) |
|||||||
| Frequency (HZ) |
50 |
|||||||
| Output voltage (V) |
400 / 230 |
|||||||
| Maximum (long-term/standby) output current (A) |
900/990 |
|||||||
| Unit dimensions (length × width × height) (mm) |
3300*1440*2160 |
|||||||
| Unit net weight (kg) |
3300 |
|||||||
| Diesel engine |
|
|||||||
| Manufacturer |
Deutz |
|||||||
| Model |
BF8M1015CP-LA G2 |
Rated speed (RPM) |
1500 |
|||||
| Number of cylinders |
8 |
Output power (kW) |
448/490 |
|||||
| Cylinder arrangement |
L |
Fuel specifications and grade |
China 0# (light diesel) |
|||||
| Bore/stroke (mm) |
132*145 |
Fuel consumption (L/h) |
83 |
|||||
| Total cylinder capacity (L) |
18.9 |
Fuel consumption (g/kwh) |
≤196 |
|||||
| Compression ratio |
17.5:1 |
Lubricating oil specifications and grade |
API-CD grade and above |
|||||
| Intake method |
Turbocharged |
Total lubricating oil capacity (L) |
48 |
|||||
| Speed control method |
Electronic speed control |
Lubricating oil consumption (L/h) |
0.38 |
|||||
| Thermostat temperature control range (°C) |
DC12V electric start |
Normal operating temperature of lubricating oil (°C) |
110 |
|||||
| Allowable maximum back pressure (KPa) |
10 |
Maximum exhaust temperature (°C) |
550 |
|||||
| Cooling method |
Closed-circuit water cooling |
Intake air flow (m3/min) |
25.9/26.7 |
|||||
| Coolant capacity (L) |
98 |
Exhaust gas flow (m3/min) |
71.6/74.5 |
|||||
| Normal operating temperature of cooling water (°C) |
83-95 |
Air consumption (m3/min) |
45.7 |
|||||
| Cooling water flow (L/sec) |
5.4 |
Radiator dimensions (length × width × height) (mm) |
310×995×1350 |
|||||
| Generator |
|
|||||||
| Manufacturer |
Jiangsu Weiming Power Equipment Co., Ltd. |
|||||||
| Model |
WM 38BD |
Excitation method |
Brushless self-excited (PMG optional) |
|||||
| Voltage adjustment range |
≥±5% |
Steady-state voltage regulation rate |
≤±1.0% |
|||||
| Temperature rise |
H |
Voltage control method |
AVR |
|||||
| Insulation class |
H |
Overload capacity |
1.5 times for 2 minutes |
|||||
| Protection class |
IP22 |
Short-circuit capacity |
3 times for 10 seconds |
|||||
| Efficiency |
93.03% |
Cooling method |
Self-cooled |
|||||
| Telephone interference coefficient |
THF<2%, TIF<50 |
Rotor type |
Salient-pole type |
|||||
Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.
Keywords:
Previous Page
Next Page
Previous Page:
Next Page:
Recommended News
What are the uses of diesel generator sets?
2020-12-26
The working principle of the generator set
2020-03-12
2020-03-12
Some precautions for using a generator
2020-03-12