WM-W250 unit technical data
Output capacity (kVA) |
312.5/343.75 |
|||||||
Output power (kW) |
250/275 |
|||||||
Power factor |
0.8 (lagging) |
|||||||
Frequency (HZ) |
50 |
|||||||
Output voltage (V) |
400 / 230 |
|||||||
Maximum (long-term/standby) output current (A) |
450/495 |
|||||||
Unit dimensions (length × width × height) (mm) |
2900*1100*1800 |
|||||||
Unit net weight (kg) |
2300 |
|||||||
Diesel engine |
|
|||||||
Manufacturer |
Weichai Power Co., Ltd. |
|||||||
Model |
WP12D317E200 |
Rated speed (RPM) |
1500 |
|||||
Number of cylinders |
6 |
Output power (kW) |
288/317 |
|||||
Cylinder arrangement |
L |
Fuel specifications and grade |
China 0# (light diesel) |
|||||
Bore/stroke (mm) |
126*155 |
Fuel consumption (L/h) |
106 |
|||||
Total cylinder capacity (L) |
18.9 |
Fuel consumption (g/kwh) |
≤195 |
|||||
Compression ratio |
17:1 |
Lubricating oil specifications and grade |
API-CD grade and above |
|||||
Intake method |
Turbocharged |
Total lubricating oil capacity (L) |
24 |
|||||
Speed control method |
Mechanical/electronic control |
Lubricating oil consumption (L/h) |
0.43 |
|||||
Thermostat adjustment temperature range (°C) |
Electric start DC12V |
Normal operating temperature of lubricating oil (°C) |
110 |
|||||
Allowable maximum back pressure (KPa) |
10 |
Maximum exhaust temperature (°C) |
550 |
|||||
Cooling method |
Closed-loop water cooling |
Intake air flow (m3/min) |
29.2/32 |
|||||
Coolant capacity (L) |
25 |
Exhaust gas flow (m3/min) |
80.7/89.3 |
|||||
Normal operating temperature of cooling water (°C) |
83-95 |
Air consumption (m3/min) |
51.5 |
|||||
Cooling water flow (L/sec) |
5.4 |
Radiator dimensions (length × width × height) (mm) |
340×1240×1510 |
|||||
Generator |
|
|||||||
Manufacturer |
Jiangsu Weiming Power Generation Equipment Co., Ltd. |
|||||||
Model |
WM 38BG |
Excitation method |
Brushless self-excited (PMG optional) |
|||||
Voltage adjustment range |
≥±5% |
Steady-state voltage regulation rate |
≤±1.0% |
|||||
Temperature rise |
H |
Voltage control method |
AVR |
|||||
Insulation class |
H |
Overload capacity |
1.5 times for 2 minutes |
|||||
Protection class |
IP22 |
Short-circuit capacity |
3 times for 10 seconds |
|||||
Efficiency |
93.31% |
Cooling method |
Self-cooled |
|||||
Telephone interference coefficient |
THF<2%, TIF<50 |
Rotor type |
Salient-pole type |
Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.