WM-S200 unit technical data
| Output capacity (kVA) | 450/500 |
||||||
| Output power (kW) |
360/400 |
||||||
| Power factor |
0.8 (lagging) |
||||||
| Frequency (Hz) |
50 |
||||||
| Output voltage (V) |
400 / 230 |
||||||
| Maximum (long-term/standby) output current (A) |
648/720 |
||||||
| Unit dimensions (length × width × height) (mm) |
3500×1485×1958 |
||||||
| Unit net weight (kg) |
3840 |
||||||
| Diesel engine |
|
||||||
| Manufacturer |
Shanghai Diesel Engine Co., Ltd. |
||||||
| Model |
SC25G610D2 |
Rated speed (RPM) |
1500 |
||||
| Number of cylinders |
12 |
Maximum output power (kW) |
: 445 |
||||
| Cylinder arrangement |
V |
Fuel specifications and grade |
China 0# (light diesel) |
||||
| Bore/stroke (mm) |
135/150 |
Fuel consumption (g/kwh) |
202 |
||||
| Total cylinder capacity (L) |
25.8 |
Lubricating oil specifications and grade |
API-CD grade and above |
||||
| Compression ratio |
16:1 |
Total lubricating oil capacity (L) |
65 |
||||
| Intake method |
Air-to-air cooling |
Lubricating oil consumption (g/kwh) |
0.4 |
||||
| Speed control method |
Electronic speed control |
Maximum exhaust temperature (°C) |
650 |
||||
| Starting method |
Electric start DC24V |
Minimum intake pressure (KPa) |
2.49 |
||||
| Allowable maximum back pressure (kPa) |
6 |
Air consumption (m3/min) |
37.6 |
||||
| Cooling method |
Water cooling |
Intake volume (m3/min) |
39.45 |
||||
| Total cooling water capacity (L) (engine capacity only) |
151 |
Exhaust Smoke(FSN) |
≤2.0 |
||||
| Maximum outlet water temperature (°C) |
95 |
Speed regulation rate (%) |
0~5 |
||||
| Cooling water flow (L/sec) |
5.82 |
Noise dB(A) |
118 |
||||
| Generator |
|
||||||
| Manufacturer |
Jiangsu Weiming Power Generation Equipment Co., Ltd. |
||||||
| Model |
WM365 |
Excitation method |
Brushless self-excited (PMG optional) |
||||
| Voltage adjustment range |
≥±5% |
Steady-state voltage regulation rate |
≤±1.0% |
||||
| Temperature rise |
H |
Voltage control method |
AVR |
||||
| Insulation grade |
H |
Overload capacity |
1.5 times for 2 minutes |
||||
| Protection grade |
IP22 |
Short-circuit capacity |
3 times for 10 seconds |
||||
| Efficiency |
93.9% |
Cooling method |
Self-cooling |
||||
| Telephone interference coefficient |
THF<2%, TIF<50 |
Rotor type |
Salient-pole type |
||||
Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.
Keywords:
Previous Page
Next Page
Previous Page:
Next Page:
Recommended News
What are the uses of diesel generator sets?
2020-12-26
The working principle of the generator set
2020-03-12
2020-03-12
Some precautions for using a generator
2020-03-12
