WM-W180 unit technical data
Output Capacity (kVA) |
225/250 |
|||||||
Output Power (kW) |
180/200 |
|||||||
Power Factor |
0.8 (Lagging) |
|||||||
Frequency (HZ) |
50 |
|||||||
Output Voltage (V) |
400 / 230 |
|||||||
Maximum (Continuous/Standby) Output Current (A) |
324/360 |
|||||||
Unit Dimensions (Length × Width × Height) (mm) |
2750*1050*1800 |
|||||||
Unit Net Weight (kg) |
2100 |
|||||||
Diesel Engine |
|
|||||||
Manufacturer |
Weichai Power Co., Ltd. |
|||||||
Model |
WP10D238E200 |
Rated Speed (RPM) |
1500 |
|||||
Number of Cylinders |
6 |
Output Power (kW) |
216/238 |
|||||
Cylinder Arrangement |
L |
Fuel Specifications and Grade |
China 0# (Light Diesel) |
|||||
Bore/Stroke (mm) |
126*130 |
Fuel Consumption (L/h) |
83 |
|||||
Total Cylinder Capacity (L) |
18.9 |
Fuel Consumption (g/kwh) |
≤195 |
|||||
Compression Ratio |
17:1 |
Lubricating Oil Specifications and Grade |
API-CD Grade and Above |
|||||
Intake Method |
Turbocharged |
Total Lubricating Oil Capacity (L) |
24 |
|||||
Speed Control Method |
Mechanical/Electronic Control |
Lubricating Oil Consumption (L/h) |
0.38 |
|||||
Thermostat Adjustment Temperature Range (°C) |
Electric Start DC12V |
Normal Operating Temperature of Lubricating Oil (°C) |
110 |
|||||
Allowable Maximum Back Pressure (KPa) |
10 |
Maximum Exhaust Temperature (°C) |
550 |
|||||
Cooling Method |
Closed-Circuit Water Cooling |
Intake Airflow (m3/min) |
25.9/26.7 |
|||||
Coolant Capacity (L) |
22 |
Exhaust Gas Flow (m3/min) |
71.6/74.5 |
|||||
Normal Operating Temperature of Cooling Water (°C) |
83-95 |
Air Consumption (m3/min) |
45.7 |
|||||
Cooling Water Flow (L/sec) |
5.4 |
Radiator Dimensions (Length × Width × Height) (mm) |
310×995×1350 |
|||||
Generator |
|
|||||||
Manufacturer |
Jiangsu Weiming Power Generation Equipment Co., Ltd. |
|||||||
Model |
WM 38BD |
Excitation Method |
Brushless Self-Excited (PMG Optional) |
|||||
Voltage Regulation Range |
≥±5% |
Steady-State Voltage Regulation Rate |
≤±1.0% |
|||||
Temperature Rise |
H |
Voltage Control Method |
AVR |
|||||
Insulation Class |
H |
Overload Capacity |
1.5 times for 2 minutes |
|||||
Protection Class |
IP22 |
Short Circuit Capacity |
3 times for 10 seconds |
|||||
Efficiency |
93.03% |
Cooling Method |
Self-Cooling |
|||||
Telephone Interference Coefficient |
THF<2%, TIF<50 |
Rotor Type |
Salient-Pole Type |
Note: The above technical data is for reference only. Our company will not be held responsible for any changes in technical parameters due to various reasons.
Keywords:
Previous Page
Next Page
Previous Page:
Next Page:
Recommended News
What are the uses of diesel generator sets?
2020-12-26
The working principle of the generator set
2020-03-12
2020-03-12
Some precautions for using a generator
2020-03-12